How to safeguard your power quality and your power drive system?
For reliability and safety reasons, you will want to protect your Medium Voltage vfd drive from disturbance from the grid, from short-circuits, overloads, etc …. But also, your mains supply must be kept healthy and safeguarded against negative impact of harmonics caused by your vfd drive.
First things first, getting the basics right:
-
-
Series-Connected H-Bridge (SC-HB) Topologies and Modular Multilevel Converter (M2C or MMC):
-
-
-
- M2C drives also allow for redundant power cells, enabling you to bypass faulty cells without affecting operation. The topology of the 12-pulse transformer with direct front end (DFE), shown on the diagram above, requires the same kind of protection means as for the 3L-NPC or 5L-ANPC drive topology. However, the fault energy in case of a short circuit in one semiconductor, feeding into the fault is very small thanks to the distributed energy storage.
-
Drives are nonlinear consumers causing harmonics
Basic diagram of voltage source inverter
The 12-pulse medium voltage source inverter below is made up of two 6 pulse rectifiers supplied by a three winding transformer. The intelligent combination of secondaries with a phase shift of 30°el, cancels harmonics (the fifth and the seventh) on the primary side.
By the way, the number of pulses determines the harmonic number by the formula: pulses* 2 +/- 1. For a 12-pulse drive this results in 12-1 =11th and 12+1 = 13th, 12*2-1= 23rd and 12*2+1=25th, etc … thereby eliminating all harmonics below the 11th.
Harmonics are often discussed in terms of a THD (total harmonic distortion) percentage. This percentage value describes how badly the waveform is distorted and deviates from a pure sinusoidal waveform. A waveform that is highly distorted will be more flat-topped and have a higher THD percentage value.
The following two formulas are used to quantify the harmonics present in a system:
THDV is the total harmonic distortion of the voltage waveform.
THDI is the total harmonic distortion of the current waveform.
Total harmonic distortion of the current (THDI) is the ratio in percentage of the total RMS (Root Mean Square) value of the harmonics over the RMS value of the current at the fundamental frequency. See formula below and practical example for a 6-pulse direct front end.
![]() |
![]() |
The voltage distortion is a consequence of the current distortion multiplied by the impedance at the point of measurement of the voltage referred to as the point of common coupling (PCC).
Udist= Idist * Z ( indeed again ohms law ;-).
If your supply system is rather weak, it will have a high impedance (Z) =>You can’t have as much current distortion (Idist) to keep the resulting voltage distortion (Vdist) at the point of common coupling within acceptable limits.
A typical use-case is the setup of the supply by the transformer in normal conditions and the switch-over to the back-up generator in case of loss of mains power. The impedance Z of a generator is about 3 times larger than the impedance of the normal supply via the transformer. If the voltage distortion may not appear as a problem when supplied by the transformer, a serious issue might arise in case of supply in generator mode. Below you see an example of a severely distorted mains voltage with multiple zero crossings. Such a distorted voltage waveform can cause unstable operation of sensitive electronics and issues with welding applications relying on zero crossing detection. The distorted line voltage might also introduce harmonic currents in other linear loads such as motors. In this use case, the harmonic analysis must be done based on a generator source, in addition to the traditional utility source analysis.
voltage distorted with multiple zero crossings
In fact, the impedance Z is a measure for the strength of the supply. But there is a much better definition for system strength used in the relevant standards such as IEEE519 and IEC 61000-2-4: the short circuit ratio (SCR). It is an indicator of the strength of a network bus short circuit current (Isc) versus the current demand of a device IL (=maximum average load current in 15- 30- minute interval over 12 months) at the point of common coupling (PCC= is the point where the utility connects the consumer).
The value of the short circuit current should be easily obtained from the utility. It can also be calculated with the aid of nameplate data of the transformer of the utility. Look for the power (P in kVA => multiply by 1000), the secondary voltage (Usec in volts) and the short circuit impedance in % (Uk also sometimes called “impedance” but always in %). Determine the secondary current (Isec) by the first formula below and obtain the network short circuit current by multiplying with 100 divided by the short circuit impedance Uk.
The following table extracted from table 10-4 of IEEE 519 (1992) advices limits on the individual current harmonics according the short circuit ratio. The higher the short circuit ratio, the higher the allowed total demand distortion (TDD). Indeed, with a high short circuit ratio, the expected voltage distortion (at PCC) caused by the nonlinear consumer becomes smaller.
By the way, a high network short circuit means a low source impedance Z. Coming back to Oms law
Udist= Idist * Z : if your supply system is rather strong, it will have a low impedance (Z) =>the current distortion (Idist) allowing the resulting voltage distortion (Vdist) at the point of common coupling, to stay within acceptable limits, can be higher.
IEEE519 table current limits harmonics as function of shortcircuit ratio at PCC
As mentioned above, the voltage distortion should be kept within safe limits at the point of common coupling. The table below, extracted from table 10-3 of IEEE 519, advices limits according to the context.
Special applications use sensitive electronics in places like hospitals, airports, data centres, or laboratories.
Dedicated systems are exclusively dedicated to the converter load.
The IEEE 519 is sometimes a bit mis-used in specification of drive requirements. Some specs impose limits to the current harmonics of the individual drive by defining the point of common coupling (PCC) of the drive on the primary (PCC3) of the converter transformer and not on the primary of the utility transformer (PCC1). The short circuit ratio will be lower when the PCC is situated right upstream of the drive (PCC3) and thereby imposing lower limits than originally advised by the IEEE 519. You might actually end up addressing a problem that doesn’t exist. In fact, IEEE 519 has not been developed for individual assessment of nonlinear consumers but for guidance in the design of power systems with nonlinear loads.
illustration of different points of common coupling with a twelve pulse drive
The IEC 61000-2-4 has a slightly different approach: the manufacturer of the variable frequency drive is to deliver the current harmonic level THC, under rated conditions, as a percentage of the rated RMS current for each order up to the 40th. The Power Drive System shall be assumed to be connected to a point of common coupling (PCC) with a short circuit ratio of RSC = 250 and with initial voltage distortion less than 1%. IEC 610000-2-4 introduces the in-plant point of coupling (IPC) to a supply network where other loads may connect. By focusing on the in-plant point of coupling (IPC), it ensures that the coordination of interference limits is effectively managed, thereby maintaining the integrity and reliability of the electrical systems. These reference levels, while not direct limit values, are categorized in classes 1 to 3.
IEC 61000-3-6 or GB/T 14549 can be used for the assessment of emission limits for distorting loads in MV power systems. In that context, there are quite some sophisticated software tools available on the market that analyse complex networks with multiple elements and various configurations of the grid.
If we lost you along the line, please contact us for a free video call
Get clarifications and answers for your PDS now.
Do not let uncertainty hold you back. Reach out for practical solutions and expert advice for your power drive system needs. Contact us today to ensure your critical machines are driven reliably, efficiently and safely.



